Loading...
HomeMy WebLinkAbout2514 Reata Pl., Diamond Bar (PR25-0519) (PC2)CITY OF DIAMOND BAR Building & Safety 2180 Copley Drive Diamond Bar, CA 91765 (909)839-7020 PLAN CORRECTION LIST 2022 California Building Standards Code and Title 24, California Administrative Code. PROJECT INFORMATION: Job: Address: 2514 REATA PL., DIAMOND BAR, CA Plan Check No.: PR25-0519 Valuation: $75,000.00 Architect: LAK DEVELOPMENT Telephone No.: 760-486-1697 Use: Occupancy: Type of Construction: Floor Areas: RESIDENTIAL R3 VB 795 Plan Reviewer: TIM TRAN , CBO, MCP, CASp 1" Review Date: 4/26/2025 Telephone #: 626-202-6869 2nd Review Date: 5/31/2025 FAX #: 909-594-2658 Email: ttpinchk@gmail.com • Provide responses to the corrections listed below onto the plans before a permit can be issued for this project. • CODES: All references pertain to the current 2022 edition of the California Building Standards Code and 2022 California Residential Code, unless otherwise noted. • All corrections shall be made to the original drawings and re -printed and submitted for re- check. Marked up plans will not be accepted. • Please return this plan checklist with the redlined set and three revised sets when you return plans and calculations for recheck. Note: For Electronic Plan Check — hard -copy plans do not need to be provided during plan check until permit is ready to issue, and further instructions will be provided by City Permit Clerk. • Please provide a notation in the margin next to each comment indicating where in the plans it has addressed! PLAN REVIEW COMMENTS Indicate Where Correction Made GENERAL 1. a stamp to thoso plans and 2. PC2: Approval recommended. ARCHITECTURAL [CBC§xxx.xxJ Al. , A2. Sheet A-2: I. II. IV. Glazing in an individual fixed or operable panel that meets all of the following conditions is considered to be a hazardous location: i. The exposed area of an individual pane is larger than 9 square feet. ii. The bottom edge of the glazing is less than 18 inches above the floor. iii. The top edge of the glazing is more than 36 inches above the floor. iv. One or more walking surfaces are within 36 inches, measured horizontally and in a straight line, of the glazing. [R308.4.3] PC2: This item appears to have not been addressed. V. VI. A3. Sheet A-3: I. Exterior side -hinged doors must be tested and labeled as conforming to AAMA/WDMA/CSA101/LS.2/A440 or comply with Section 1709.5.2. [1709.5.1] PC2: This item appears to have not been addressed. Exterior wood door must be 1- 3/4" thick. II. the i. ii. D:\RKA\RKA Projects 2025\Due 6-3-25 Diamond Bar PR25-0519 pc2\2514 Reata PI., Diamond Bar (PR25-0519) (PC2).docx Page 2 of 4 Indicate Where Correction Made III. Where balconies or other elevated walking surfaces are exposed to water from direct or blowing rain, snow, or irrigation, and the structural framing is protected by an impervious moisture barrier, the construction documents must include details for all elements of the impervious moisture barrier system. The construction documents must include manufacturer's installation instructions. [R106.1.6] PC2: This item appears to have not been addressed. IV. Where balconies or other elevated walking surfaces are exposed to water from direct or blowing rain, snow, or irrigation, and the structural framing is protected by an impervious moisture barrier, all elements of the impervious moisture barrier system must not be concealed until inspected and approved. [R109.1.5.3] PC2: This item appears to have not been addressed. (Annotate on plan.) V. Enclosed framing in exterior balconies and elevated walking surfaces that are exposed to rain or drainage from irrigation must be provided with openings that provide a net -free cross ventilation area not less than 11150 of the area of each separate space. [R317.1.3] PC2: This item appears to have not been addressed. (Provide the required ventilation.) A4. 01�� I. 11. Approved corrosion -resistant flashing must be applied shingle fashion in a manner to prevent entry of water into the wall cavity or penetration of water to the building structural framing components. Self -adhered membranes used as flashing must comply with AAMA 711. Fluid -applied membranes used as flashing in exterior walls must comply with AAMA 714. The flashing must extend to the surface of the exterior wall finish. Approved corrosion -resistant flashings must be installed at the following locations: i. Exterior window and door openings. Flashing at exterior window and door openings must be installed in accordance with Section R703.4.1. ii. At the intersection of chimneys or other masonry construction with frame or stucco walls, with projecting lips on both sides under stucco copings. iii. Under and at the ends of masonry, wood or metal copings and sills. iv. Continuously above all projecting wood trim. V. Where exterior porches, decks or stairs attach to a wall or floor assembly of wood - frame construction. vi. At wall and roof intersections. [R703.4] PC2: A detail reflecting this location is required. STRUCTURAL [CBCUxx.xxl S1. I. IL " III. IV. DARKA\RKA Projects 2025\Due 6-3-25 Diamond Bar PR25-0519 pc2\2514 Reata PI., Diamond Bar (PR25-0519) (PC2).docx Page 3 of 4 Indicate Where Correction Made S2. , S3. . S4.or- higher- of spaee S5. S6. PC2: Please provide elevator pit floor design to withstand an impact load of 6400 lbs. and load bearing walls to sustain elevator rail reactions per manufacture drawing. ENERGY BUILDING CODE [CEnQxxx.xxl E1. Approval recommended. GREEN BUILDING CODE [CGBSQxxx.xx] G1. Approval recommended. MECHANICAL [CNIQxxx.xx] M 1. Provide mechanical plans. M2. PC2: This item appears to have not been addressed. Sheet ME-1 is missing. ELECTRICAL [CEQxxx.xx] El. Provide electrical plans. E2. PC2: This item appears to have not been addressed. Sheet ME-1 is missing. PLUMBING [CPC&xxx.xxI P 1. N/A. D:\RKA\RKA Projects 2025\Due 6-3-25 Diamond Bar PR25-0519 pc2\2514 Reata PI., Diamond Bar (PR25-0519) (PC2).docx Page 4 of 4