HomeMy WebLinkAbout552442 PHILIPS ADVANCE BALLAST.pdfRevised 02/12/2008
Data is based upon tests performed by Philips Lighting Electronics N.A. in a controlled environment and is representative of relative performance. Actual performance can vary
depending on operating conditions. Specifications are subject to change without notice. All specifications are nominal unless otherwise noted.
PHILIPS LIGHTING ELECTRONICS N.A.
10275 WEST HIGGINS ROAD · ROSEMONT, IL 60018
Tel: 800-322-2086 · Fax: 888-423-1882 · www.philips.com/advance
Customer Support/Technical Service: 800-372-3331 · OEM Support: 866-915-5886
ICF-2S42-M2-LD@120
Brand Name SMARTMATE
Ballast Type Electronic
Starting Method Programmed Start
Lamp Connection Series
Input Voltage 120-277
Input Frequency 50/60 HZ
Status Active
Electrical Specifications
Lamp Type Num.
of
Lamps
Rated
Lamp Watts
Min. Start
Temp (°F/C)
Input
Current
(Amps)
Input
Power
(ANSI
Watts)
Ballast
Factor
MAX
THD
%
Power
Factor
MAX Lamp
Current
Crest Factor
B.E.F
.
* (1) FC9T5 & (1)
FC12T5
2 62 0/-18 0.51 61 0.85 10 0.98 1.5 1.39
Wiring Diagram
WIRING: (2) LAMPS (1) LAMP
Green Terminal must be Grounded
GREEN
BLACK
WHITE BALLASTLINE
BLUE
RED
YELLOW
RED
BLUE
The wiring diagram that appears above is
for the lamp type denoted by the asterisk (*)
Standard Lead Length (inches)
in.cm.
Black 0.0
White 0.0
Blue 0.0
Red 0.0
Yellow 0
Gray
Violet
in.cm.
Yellow/Blue
Blue/White
Brown
Orange
Orange/Black
Black/White
Red/White
Enclosure
Enclosure Dimensions
OverAll (L)Width (W)Height (H)Mounting (M)
4.98 "3.00 "1.29 "4.60 "
4 49/50 3 1 29/100 4 3/5
12.6 cm 7.6 cm 3.3 cm 11.7 cm
ICF-2S42-M2-LD@120
Brand Name SMARTMATE
Ballast Type Electronic
Starting Method Programmed Start
Lamp Connection Series
Input Voltage 120-277
Input Frequency 50/60 HZ
Status Active
Electrical Specifications
Notes:
Section I - Physical Characteristics
1.1 Ballast shall be physically interchangeable with standard electromagnetic or standard electronic ballasts, where applicable.
1.2 Ballast shall be available in a plastic/metal can or all metal can construction to meet all plenum requirements.
1.3 Ballast shall be provided with poke-in wire trap connectors color coded per ANSI C82.11.
Section II - Performance Requirements
2.1 Ballast shall be Programmed Start except for ballasts with -QS suffix, which shall be Rapid Start.
2.2 Ballast shall contain auto restart circuitry in order to restart lamps without resetting power.
2.3 Ballast shall operate from 50/60 Hz input source of 120V through 277V with sustained variations of +/- 10% (voltage and frequency).
2.4 Ballast shall be high frequency electronic type and operate lamps at a frequency above 42 kHz to avoid interference with infrared devices
and eliminate visible flicker.
2.5 Ballast shall have a Power Factor greater than 0.98 for primary lamp.
2.6 Ballast shall have a minimum ballast factor of 1.00 for primary lamp application.
2.7 Ballast shall provide for a Lamp Current Crest Factor of 1.7 or less.
2.8 Ballast input current shall have Total Harmonic Distortion (THD) of less than 10% when operated at nominal line voltage with primary lamp.
2.9 Ballast shall have a Class A sound rating.
2.10 Ballast shall have a minimum starting temperature of -18C (0F) for primary lamp. Ballasts for PL-H lamps shall have a minimum starting
temperature of -30C (-20F) for primary lamp.
2.11 Ballast shall provide Lamp EOL Protection Circuit.
2.12 Ballast shall tolerate sustained open circuit and short circuit output conditions.
Section III - Regulatory Requirements
3.1 Ballast shall not contain any Polychlorinated Biphenyl (PCB).
3.2 Ballast shall be Underwriters Laboratories (UL) listed, Class P and Type 1 Outdoor; and Canadian Standards Association (CSA) certified
where applicable.
3.3 Ballast shall be rated for use in air-handling spaces.
3.4 Ballast shall comply with ANSI C62.41 Category A for Transient protection.
3.5 Ballast shall comply with ANSI C82.11 where applicable.
3.6 Ballast shall comply with the requirements of the Federal Communications Commission (FCC) rules and regulations, Title 47 CFR part 18,
Non-Consumer (Class A) for EMI/RFI (conducted and radiated).
3.7 Ballast shall comply with NEMA 410 for in-rush current limits.
Section IV - Other
4.1 Ballast shall be manufactured in a factory certified to ISO 9001 Quality System Standards.
4.2 Ballast shall carry a five-year warranty from date of manufacture against defects in material or workmanship, including replacement, for
operation at a maximum case temperature of 75C and three-years for a maximum case temperature of 85C (90C three-year warranty for ICF-
1H120-M4-XX, ICF-2S42-90C-M2-XX and ICF-2S70-M4-XX models).
4.3 Manufacturer shall have a twenty-year history of producing electronic ballasts for the North American market.
Revised 02/12/2008
Data is based upon tests performed by Philips Lighting Electronics N.A. in a controlled environment and is representative of relative performance. Actual performance can vary
depending on operating conditions. Specifications are subject to change without notice. All specifications are nominal unless otherwise noted.
PHILIPS LIGHTING ELECTRONICS N.A.
10275 WEST HIGGINS ROAD · ROSEMONT, IL 60018
Tel: 800-322-2086 · Fax: 888-423-1882 · www.philips.com/advance
Customer Support/Technical Service: 800-372-3331 · OEM Support: 866-915-5886