February 20, 1978
County of Los Angeles
Department of the County Engineer
Soils Engineering Section
550 South Vermont
Los Angeles, California 90020
Attention: Mr. Charles F. Ruggles
Subject: Response to Soils Engineering Section Review Sheet,
dated February 6, 1978, Tracts 34160 and 34161,
Parent Tract 29053), Diamond Bar Area,
County of Los Angeles
Reference: Report by S. E. Medall & Associates, Inc.,
dated December 19, 1977
Dear Mr. Ruggles:
As discussed in our conversation of February 15, 1978, the
following comments are presented relative to the remarks
provided in the subject review sheet. For our cross
sections, Y-Y and HH-HH, the county has indicated that
according to these geologic cross sections, the bedding
planes reverse directions beneath the buttress. The
calculations for potential failure beneath the buttress
key does not reflect this condition, please reanalyze.
As discussed in our aforementioned conversation, these cross
sections are two-dimensional representations of three-
dimensional conditions that actually become more favorable in
a down slope direction. When reviewing such two-dimensional
E,,,NGHNJEER1NG GEOLOGY
S PC TI
County of Los Anyclos
Page 2
February 20, 1978
cross sections, care must be taken not to misinterpret
the geotechnical significance of apparent dip conditions.
It is our opinion that our assumption of linear planar
conditions is a very conservative approximation that does
not warrant further refinement. The conservative nature
of our evaluation of the Y-Y cross section should be
further evident upon review of this cross section's
orientation relative to the orientation of the proposed
slope surface. The oblique angle of the slope in the cross
section would suggest at most, a wedge type potential
instability whereas our analyses assume the infinite slope
condition.
For our section Z-Z, the county has indicated that the
calculations submitted using the Sultan -Seed method failed
to recognize that the contact plane between the active and
passive wedges traversed different soils. Shear values
for the. stronger soils were used throughout. Using correct
shear values, this section may not meet county standards.
We recognize that it can be argued that since we utilized
bedrock shear strengths through an area which actually
contained bedrock and compacted fill, the assumption of
S. E. Medall & Associates, Inc.
County of Los Angeles February 20, 1978
Page 3
bedrock shear strength may not be a conservative assumption.
In consideration, however, of the numerous compounding
conservative assumptions that must be made to make such a
three-dimensional stability evaluation statically determinant,
it is our opinion that the assumption made was a reasonable
assumption and the resulting design adequate. In consideration
of the county's concern, however, we have re-evaluated the
buttress requirements for the cross section. In order to
establish static equilibrium in conformance with minimum
county criteria, two feet was added to the previously
recommended key depth.
For cross section FF-FF, the county has indicated that
according to this section, the outer shear key slope (lower
slope) will exceed 12:1 horizontal to 1 vertical. This
exceeds the minimum requirement of the county code and must
be analyzed.
on this cross section FF-FF, existing and proposed grading
contours were indicated along with the corresponding geologic
information underlying that area. The shear key requirement
of this area was recognized upon review of this section and
subsequently analyzed. Regrading of this slope for the
S. E. Medall & Associates, Inc.
County of Los Angeles
Page 4
February 20, 1978
installation of the recommended shear key should be
performed in accordance with the recommendations which
accompany the referenced report. Therein, it is indicated
that all cut and fill slopes proposed onsite should not
exceed 11-2:1 (horizontal to vertical) slope ratio.
It is hoped that the information contained herein is
sufficient to satisfy the county's questions and concerns
relative to the soils engineering information contained in
the referenced report. Should the county have any further
questions, however, please do not hesitate to call.
Respectfully submitted,
S. E. MEDALL & ASSOCIATES, INC.
Gregory Axten,
Director of Engineering Services
GWA: j mb
c: (3) Addressee
3) Weatherfield Homes
Atten: Mr. Al Blunt
Encl: Buttress Calculations - Section Z-Z1
S. E. Medall & Associates, Inc.
a °'f
r
i '
i
CIP7 5 =
OP1 , 5,;5
1'2'5rQvm FS,
2c-
S. E. Medal[ & Associates, Inc.
Consultants in the Earth Sciences
3030 So. Bundy Er., L., An Bales, C.. 90066 (213) 390-4079
2168 So. Hathaway St., Santa An., Ca. 9270, (714) 546-6602
DATE BY
W.O. SCALE
9,
05es
I ' "
053uoj-d F, S'
S. E. Medall & Associates, Inc.
Consultants in the Earth Sciences
3030 So. Bundy Or,, Los Anget-, Ca. 90066, (213) 390-4079
2168 So. Hathaway St., Santa Ana, Co. 92705, (714) 546-6602
DATE
r-_ I " I 'C'
I I BY
oSCALEW.O.